Building Technologies Boiler sequence controller RMK770 CE1P3132en
HVAC Products 3 Commissioning 23.04.2009
With the analog inputs, the following settings can be made:
Type
Measuring range
Measured value correction
Temperature sensor LG-Ni1000 is preselected as standard for all types of temperature
sensors.
The following types of input signals can be handled:
LG-Ni1000
2 × LG-Ni1000
T1
Pt1000
DC 0…10 V
Main menu > Commissioning > Settings > … or
Main menu > Settings > Inputs > …X…
Operating line Range Factory setting
Type Ni1000 / 2×Ni1000 / T1 /
Pt1000 / 0…10 V
Ni1000
Passive temperature signals delivered by LG-Ni1000 sensing elements have a
measuring range of 50…+250 °C
Passive temperature signals delivered by 2 x LG-Ni1000 or T1 sensing elements
have a measuring range of 50…+150 °C
Passive temperature signals delivered by Pt1000 sensing elements have a measur-
ing range of 50…+400 °C
In the case of active signals, the measuring range can be selected. To be entered is
a low and a high limit value.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Inputs > …X…
Operating line Range Factory setting
Value low Depending on the
selected type
Depending on
the type
Value high Depending on the
selected type
Depending on
the type
Flow temperature with an active signal of DC 0…10 V = 0…100 °C:
Low limit value: 0 °C
High limit value: 100 °C
With a passive temperature sensor, the measured value can be readjusted by 3.0 to
+3.0 K to compensate for line resistance. It is thus possible to make onsite calibrations
with a reference instrument.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Inputs > …X…
Operating line Range Factory setting
Correction 3.0…+ 3.0 K 0.0 K
When the Commissioning menu is quit, a check is made to see which sensors are con-
nected. If, later, one of the sensors connected at this point in time is missing, or if there
is a short-circuit, a fault status message "[…X…] sensor error" will be delivered.
If there is an open-circuit of the measuring line, the operator unit displays the measured
value as: ----.
A short-circuit is displayed as: oooo.
Analog inputs
Type
Setting
Measuring range
Setting
Example
Measured value
correction
Setting
Fault handling