Building Technologies Boiler sequence controller RMK770 CE1P3132en
HVAC Products 6 Boiler sequence management 23.04.2009
If there is no main flow temperature sensor, the following configuration adopts the meas-
ured value inside the controller from the boiler sensor of the current lead boiler:
Main menu > Commissioning > Extra configuration > Boiler sequence manager > Inputs > Main
flow sensor: autonomous
This variant can only be used with dual-boiler plant.
The main return temperature sensor is highly recommended in connection with a
pressureless header; but its configuration can also be deleted.
In the extra configuration, the basic configuration can be complemented and/or
amended.
Main menu > Commissioning > Extra configuration > Boiler sequence manager > Inputs
Operating line Adjustable values / remarks
Main flow sensor Terminal marking / autonomous
Main return sensor
Consumer return sensor Return sensor on the consumer side
[Main pump] overload Digital input for fault supervision of main
pump
[Main pump B] overload Digital input for fault supervision of main
pump B (with twin pumps)
Flow signal Digital input for flow supervision of main
pump
MBRT return sensor Sensor for maintained main return tempera-
ture
Fault input 1 Digital input for fault supervision of boiler
sequence
Fault input 2 Digital input for fault supervision
Fault input 3 Digital input for fault supervision
Boil sequence selection input 1 Control input 1 for boiler sequence selection
Boil sequence selection input 2 Control input 1 for boiler sequence selection
Boil sequence selection input 3 Control input 1 for boiler sequence selection
Release input Release input for the boiler sequence
Summer operation input Digital input for summer operation
Heat request modulating
Heating curve request 2-pos
DHW request 2-pos DHW request 2-pos
Frost prot request 2-pos
Main menu > Commissioning > Extra configuration > Boiler sequence manager > Outputs
Operating line Adjustable values / remarks
Main pump
Main pump B
Maint boiler return temp 3-pos
Maint boiler return temp mod
Summer operation relay
In the extra configuration, additional functions can be activated for the basic func-
tionality of the selected plant type (for more detailed information, refer to the follow-
ing section).
Extra configuration
Inputs