Model 4821/4820 Control/Communicator Installation Manual
7-6 150967
7.3 Ademco Contact ID Event Codes
Table 7-3 lists the Ademco Contact ID event codes that the 4821/4820 can send.
In the “Event Qualifier” column: 1 = New event
3 = Restore event
Table 7-3: Contact ID Event Codes
Event
Code
Event Qualifier
Group
Number
Contact/User # SIA Event Description
101 1 00 Zone # Emergency Alarm
101 3 00 Zone # Emergency Alarm Restore
110 1 00 Zone # Fire Alarm
110 3 00 Zone # Fire Alarm Restore
113 1 00 Zone # Sprinkler Alarm
113 3 00 Zone # Sprinkler Alarm Restore
114 1 00 Zone # Heat Alarm
114 3 00 Zone # Heat Alarm Restore
115 1 00 Zone # Fire Contact Alarm
115 3 00 Zone # Fire Contact Alarm Restore
120 1 00 Zone # Panic Alarm
120 3 00 Zone # Panic Alarm Restore
121 1 00 User # Duress Trigger Alarm
121 1 00 Zone # Holdup Alarm
121 3 00 Zone # Holdup Alarm Restore
130 1 00 Zone # Burglary Alarm
130 3 00 Zone # Burglary Alarm Restore
134 1 00 Zone # Door Monitor or Egress Alarm
134 3 00 Zone # Door Monitor/Egress Alarm Restore
137 1 00 Zone # Tamper Alarm
137 3 00 Zone # Tamper Alarm Restore
140 1 00 Zone # Undefined Alarm
140 3 00 Zone # Undefined Alarm Restore
151 1 00 Zone # Gas Alarm
151 3 00 Zone # Gas Alarm Restore
153 1 00 Zone # Cold Alarm
153 3 00 Zone # Cold Alarm Restore
154 1 00 Zone# Water Alarm
154 3 00 Zone# Water Alarm Restore