The 4100U or 4100ES panel serves as the system controller for the Simplex Smoke Control
System.
It controls the communications between the other system components within the smoke control
system. This panel can be used in a dedicated or a non-dedicated smoke control application.
The 4100U/4100ES connects to other panels in the following ways:
The panel can connect to other Simplex Fire Alarm Control Panels via network communications.
The can also connect to the FSCS using Remote Unit Interface (RUI) serial supervised communications
channel connections.
The Master Controller provides system control, synchronization, and supervision of all modules,
continuously scanning each module for status changes. Features include:
Operator Panel with LCD and operator keys.
Battery Charger for up to 125 Ah Batteries.
Batteries up to 50 Ah may be mounted in the bottom of the control cabinet
Batteries larger than 50 Ah mount external to main control cabinet
Compatible with Lead Acid or NiCad Batteries
System Power Supply (SPS), Power Limited:
Supplies 9 A of alarm current and 5 A of standby current.
Two Class A or Class B NACs rated at 3 A each. Supports TrueAlert non-addressable
A/V operation without synch cube.
One 24 V auxiliary power tap, under software control.
Charges 125 Ah batteries per UL 864; 55 Ah batteries per ULC S527.
LCD readout of system voltage and current, battery voltage and current, and NAC current.
Integral 250 point IDNet™ channel.
AC input is 4A @ 120 VAC, 60 Hz; 2A @ 220/230/240 VAC, 60 Hz.
Includes one relay, DPDT, 2A @ 32 VDC
Landing point and control interface for optional two circuit City Card or three circuit
Relay Card. City Card is Reverse Polarity or Local Energy, configurable for alarm,
trouble, and supervisory.
General Operating Specifications
Humidity: Up to 93% RH, Non-Condensing @ 90° F (32° C) Maximum
Temperature: 32° F to 120° F (0° C to 49° C)
4100U/4100ES Panels
4100U/4100ES Panel
FigureTag FD4-465-
02
Press ACK located unde r flashing i ndicator .
Repeat operation until all events are acknowledged.
Local tone will silence.
A B C
AC Power
D E F G H I
J K L M N O P Q R
'SP' ( ) , 0 :
S T U V W X Y Z /
ALARMS
Fire Alarm Priority 2 Alarm
SYSTEM WARNINGS
Supervisory Trouble
Alarm Silenc ed
Emergency Operating Instructions
Alarm or Warning Condition
How to Acknowledge / View Events
How to Silence Building Signals
System in dicat or fl as hing. T one On. Press Alarm Silen ce.
How to Reset System
Press System Res et.
Press Ack to silence tone device.
ZONE
1
SIG
2
AUX
3
FB
4
IO
5
IDNet
6
P
7
A
8
L
9
NET ADDR
0
DEL
Enter C/Exit
Fire Alarm
Ack
Priority 2
Ack
Supv
Ack
Trouble
Ack
Alarm
Silence
System
Reset
Event
Time
Enable
On
Arm
Disable
Off
Disarm
Auto
Lamp
Test
More
Info
Menu
Previous
Next
SYSTEM IS NORMAL
08:23: 43 am MON 11- DEC-00
Fire Control
(4100U Panel)

Table of Contents

Other manuals for Simplex 4100U

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100U and is the answer not in the manual?

Simplex 4100U Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
Max Signaling Line Circuits (SLC)2
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes
Communication ProtocolRS-232, RS-485
Battery Backup24 VDC
NAC Outputs4
Signaling Line Circuits (SLCs)2
Power Supply Current3.0 A
Max Notification Appliance Circuits (NAC)4
Max Releasing Circuits4
Max Relay Circuits4
Communication PortsRS-232, RS-485