Pre-alarm limits are:
When the flow increases 1 l/min + (3 l/min-1 l/min) * 80% = 2.6 l/min
When the flow decreases 1 l/min + (0,5 l/min-1 l/min) * 80% = 0,6 l/min
Example 2:
- Nominal value is set to 1 l/min.
- Low alarm limit is set to 0,5 l/min.
- Lower pre-alarm value is 0,7 l/min.
Pre-alarm limit will be set to:
(1 l/min – 0,7 l/min) / (1 l/min – 0,5 l/min) * 100 = 60%’
10.4.4 Optional flow meter- specific settings
When the monitor has an optional circuit board, mA -output module, there will be two extra codes
SCL and SCH visible for scaling the analog outputs. See chapter 14.3.2 mA -output module
10.4.5 Flow meter shutdown and start-up
A flow meter is shut down by setting the nominal flow rate and both alarm limits to zero (0.00). Flow meter
LEDs are turned off, its measuring values cannot be displayed and the flow meter causes no alarm output.
Shutting down a flow meter does not have any effect on the oil flow going through it.
A flow meter can be started-up by setting the nominal flow rate and the alarm limits to non-zero values.