10.5.4 Pre-alarm limit
Pre-alarm limit, i.e. the limit when outermost green LED’s are lit, can be set as a percentage from the subtrac-
tion of nominal value and alarm limit.
1 Press SET-key, until text PrS is displayed, toggling with the current set value.
2 Use arrow keys to set the percentage.
3 Exit setting mode or adjust other settings.
If optional Relay-CAN module is installed, pre-alarm limit parameter is used also to control the pre-alarm re-
lays in alarm modes DL and DHL. See chapter 14.1 Relay-CAN module.
10.5.5 Alarm mode of Relay-CAN module
This setting is visible only, if optional Relay-CAN module has been installed.
One of the alarm mode codes is on display: SL, SHL, DL, DHL, HL or C.
Select the code by mode button. See chapter 14.1 Relay-CAN module.
10.5.6 CAN-bus ID-number
The ID-number setting is valid only, when optional CAN module or Relay-CAN module is installed and the
monitor is connected to CAN-bus. If CAN bus is not used, the ID-number can be set to any value.
If the monitors are connected to CAN-bus, every monitor has a unique CAN ID-number 1…100 for communi-
cation.
More information in SKF Flowline monitor CAN interface manual.