5.1 Requirements for Mounting
5.1.1 Requirements for the Mounting Location
Grid operator registration requirement
Find out from the grid operator whether there is a registration requirement, and register the
charging station with the grid operator if required.
WARNING
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires. This can result in death or serious
injury.
Do not mount the product in areas containing highly flammable materials or gases.
Do not mount the product in potentially explosive atmospheres.
A solid, flat support surface must be available for mounting.
The support surface for installation must be made of a non-flammable material.
Do not mount the inverter on a pillar.
Installation must be carried out so that the charging port is always at a height of 1.2 m to 1.5
m above floor level (see Section5.1.4, page31).
The installation site must be selected so that the product and the vehicle can be connected with
the charging cable. The charging cable must not be strained, squeezed or bent.
No other device may be installed under the product.
The product should be mounted in such way that display messages and LED signals can be
read without difficulty (see Section5.1.4, page31).
The mounting location must be suitable for the weight and dimensions of the product.
The installation site must be less than 2000m above mean sea level.
The installation site can be exposed to direct solar irradiation. There is, however, the possibility
that the product reduces its power output to avoid overheating due to high temperatures.
The installation site should be freely and safely accessible at all times without the need for any
auxiliary equipment (such as scaffolding or lifting platforms). Non-fulfillment of these criteria
may restrict servicing.
All ambient conditions must be met (see Section15.9, page103).
The ambient temperature should be considered (see Section15.4, page101) to ensure
optimal operation.