234# Gen Control
No. Name Description Value Explanation Default
value
234.01 GnVtgMin Minimum generator voltage
in V (expert mode)
172.5 V to
210.01 InvVtgNom
‒ 172.50 V
234.02 GnVtgMax Maximum generator voltage
in V (expert mode)
210.01 InvVtgNom
to 264.5 V
‒ 250.0 V
234.03 GnCurNom Nominal generator current
in A
0.0 A to 50.0 A 1 Sunny Island 16.0 A
0.0 A to 100.0 A 2 Sunny Island
inverters parallel
16.0 A
0.0 A to 150.0 A 3 Sunny Island
inverters parallel
16.0 A
0.0 A to 50.0 A Three-phase 16.0 A
0.0Ato 80.0A Multicluster Box 6 60.0A
0.0 A to 160.0 A Multicluster Box 12 160.0 A
0.0 A to 500.0 A Multicluster Box 36 435.0 A
234.04 GnFrqNom Nominal generator frequency
under nominal load in Hz
(expert mode)
234.05 GnFrqMin
to
234.06 GnFrqMax
230 V / 50 Hz 50.00 Hz
220 V / 60 Hz 60.00 Hz
234.05 GnFrqMin Minimum generator frequency
in Hz (expert mode)
40.00 Hz to
234.04 GnFrqNom
230 V / 50 Hz 44.64 Hz
50.00 Hz to
234.04 GnFrqNom
220 V / 60 Hz 50.00 Hz
234.06 GnFrqMax Maximum generator
frequency in Hz (expert mode)
234.04 GnFrqNom
to 70.00 Hz
230 V / 50 Hz 60.00 Hz
220 V / 60 Hz 70.00 Hz
234.07 GnStrMod Generator interface Manual Manual Autostart
Autostart Automatic
234.08 GnOpTmMin Minimum run time of generator
in minutes
0 min to 360 min ‒ 15 min
234.09 GnStpTmMin Minimum stop time of the
generator in minutes
0 min to 360 min ‒ 15 min
234.10 GnCoolTm Cooling time of the generator
in minutes
0 min to 60 min ‒ 5 min
234.11 GnErrStpTm Stop time of the generator in
the event of an error in hours
(expert mode)
0 h to 24 h ‒ 1 h
234.12 GnWarmTm Warm-up time in seconds 5 s to 900 s ‒ 60 s
234.13 GnRvPwr Active power of the generator
reverse power in W (expert
mode)
0 W to 5,000 W 1 Sunny Island or
single-cluster system
100 W
0Wto 20,000W Multicluster system 100W