13 Directory of the Parameters in Installer Mode and Expert Mode SMA Solar Technology AG
106 SI60H-80H-BE-en-20 Operating Manual
235# Gen Start
234.14 GnRvTm Permissible time for reverse
power or reverse current, in s
(expert mode)
0 s to 900 s 30 s
234.15 GnCtlMod Generator control (expert
mode)
The generator control limits the
consumption of generator
current.
Cur Fixed limiting value
for current limitation
Cur
CurFrq Frequency-dependent
current limitation
234.20 GnAlSns Anti-islanding sensitivity
(expert mode)
Low Low Normal
Medium Medium
Normal Normal
High High
234.41 GnCurCtlMod Enable I-Loop in generator
mode (expert mode)
I-Loop enables generators with
inadequate voltage regulation
to be used in the system.
Droop Standard generator
operation without
I-Loop
Droop
CurCtl Current-controlled
generator operation
with I-Loop
No. Name Description Value Explanation Default
value
235.01 GnAutoEna Automatic restart of generator in
the event of disturbance
Off Disable On
On Enable
235.02 GnAutoStr Number of attempts to carry out
automatic restart of generator
(expert mode)
0to 10 3
235.03 GnSocTm1Str SOC limiting value for generator
request in interval 1 in %
Interval 1 begins at time
235.07 GnTm1Str
1% to 235.04
GnSocTm1Stp
‒40%
235.04 GnSocTm1Stp SOC limiting value for end of
generator request in interval 1
in %
Interval 1 begins at time
235.07 GnTm1Str.
235.03
GnSocTm1Str to
95%
‒80%
235.05 GnSocTm2Str SOC limiting value for generator
request in interval 2 in %
Interval 2 begins at time
235.08 GnTm2Str.
1% to 235.06
GnSocTm2Stp
‒40%
No. Name Description Value Explanation Default