SMA Solar Technology AG 13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual SI60H-80H-BE-en-20 107
235.06 GnSocTm2Stp SOC limiting value for end of
generator request in interval 2
in %
Interval 2 begins at time
235.08 GnTm2Str.
235.05 GnSocTm2
Str to 95%
‒80%
235.07 GnTm1Str Start of interval 1 for grid request
in hh:mm:ss
00:00:00 to
23:59:59
‒00:00:00
235.08 GnTm2Str Start of interval 2 for grid request
in hh:mm:ss
00:00:00 to
23:59:59
‒00:00:00
235.09 GnPwrEna Load-dependent generator
request (expert mode)
Disable Disable Enable
Enable Enable
235.10 GnPwrStr Limiting value for load-dependent
generator request in kW (expert
mode)
235.11 GnPwrStp
to 300.0 kW
‒4.0 kW
235.11 GnPwrStp Limiting value for end of
load-dependent generator
request, in kW (expert mode)
0.0 kW to
235.10 GnPwrStr
‒2.0 kW
235.12 GnPwrAvgTm Averaging time for
load-dependent generator
request in s (expert mode)
1 s to 900 s 60 s
235.13 GnTmOpEna Time-controlled generator
operation
Disable Disable Disable
Enable Enable
235.14 GnTmOpStrDt Start date for time-controlled
generator operation
in dd.mm.yyyy
01.01.2011
235.15 GnTmOpStrTm Time at the start of time-controlled
generator mode in hh:mm:ss
00:00:00 to
23:59:59
‒00:00:00
235.16 GnTmOpRnDur Run time for time-controlled
generator operation in hh:mm:ss
00:00:00 to
99:59:00
‒00:00:00
235.17 GnTmOpCyc Repeat cycle for time-controlled
generator operation
Single Once Single
Daily Daily
Weekly Weekly
235.18 GnStrChrgMod Generator request in configured
charge mode (expert mode)
Off Off Both
Full Full charge
Equal Equalization
charge
Both Full and
equalization
charge
235.19 GnStrDigIn Generator request in response to
signal on activated digital input
(expert mode)
Disable Disable Disable
Enable Enable