13 Directory of the Parameters in Installer Mode and Expert Mode SMA Solar Technology AG
110 SI60H-80H-BE-en-20 Operating Manual
242# Load
241.01 Rly1Op Function of
multifunction relay 1
(continued)
GndSwt Triggering of the grounding in the battery
backup system
AutoGn
241.02 Rly2Op Multifunction relay 2
function
See 241.01 Rly1Op, page 108 for value and explanation AutoLodExt
No. Name Description Value Default
value
241.07 ExtPwrDerMinTm Minimum time for the ExtPwrDer function of the multifunction
relay in minutes
0minto
600 min
10 min
241.08 ExtPwrDerDltVtg Voltage difference for the ExtPwrDer function of the
multifunction relay in V
The voltage difference corresponds to the cell voltage of the
battery.
0Vto
0.40 V
0.15 V
No. Name Description Value Default
value
242.01 Lod1SocTm1Str SOC limiting value for starting load
shedding 1 in interval 1 in %
Interval 1 begins at time
242.05 Lod1Tm1Str.
1% to 242.02
Lod1SocTm1Stp
30%
242.02 Lod1SocTm1Stp SOC limiting value for stopping load
shedding 1 in interval 1 in %
Interval 1 begins at time
242.05 Lod1Tm1Str.
242.01 Lod1SocTm1Str
to 90%
50%
242.03 Lod1SocTm2Str SOC limiting value for starting load
shedding 1 in interval 2 in %
Interval 2 begins at time
242.06 Lod1Tm2Str.
1% to 242.04
Lod1SocTm2Stp
30%
242.04 Lod1SocTm2Stp SOC limiting value for stopping load
shedding 1 in interval 2 in %
Interval 2 begins at time
242.06 Lod1Tm2Str.
242.03 Lod1SocTm2Str
to 90%
50%
242.05 Lod1Tm1Str Start of interval 1 for load shedding 1,
in hh:mm:ss
00:00:00 to 23:59:59 ‒
242.06 Lod1Tm2Str Start of interval 2 for load shedding 1,
in hh:mm:ss
00:00:00 to 23:59:59 ‒
242.07 Lod2SocTm1Str SOC limiting value for starting load
shedding 2 in interval 1 in %
Interval 1 begins at time
242.11 Lod2Tm1Str.
1% to
242.08 Lod2SocTm1Stp
30%
No. Name Description Value Explanation Default
value