SMA Solar Technology AG 13 Directory of the Parameters in Installer Mode and Expert Mode
Operating Manual SI60H-80H-BE-en-20 111
243# Timer
242.08 Lod2SocTm1Stp SOC limiting value for stopping load
shedding 2 in interval 1 in %
Interval 1 begins at time
242.11 Lod2Tm1Str.
242.07 Lod2SocTm1Str
to 90%
50%
242.09 Lod2SocTm2Str SOC limiting value for starting load
shedding 2 in interval 2 in %
Interval 2 begins at time
242.12 Lod2Tm2Str.
1% to
242.10 Lod2SocTm2Stp
30%
242.10 Lod2SocTm2Stp SOC limiting value for stopping load
shedding 2 in interval 2 in %
Interval 2 begins at time
242.12 Lod2Tm2Str.
242.09 Lod2SocTm2Str
to 90 %
50%
242.11 Lod2Tm1Str Start of interval 1 for load shedding 2
in hh:mm:ss
00:00:00 to 23:59:59 00:00:00
242.12 Lod2Tm2Str Start of interval 2 for load shedding 2
in hh:mm:ss
00:00:00 to 23:59:59 00:00:00
No. Name Description Value Explanation Default
value
243.01 RlyTmr1StrDt Start date for timer 1 in dd.mm.yyyy ‒ ‒ 01.01.2011
243.02 RlyTmr1StrTm Start time at which the multifunction
relay activates for timer 1 in hh:mm:ss
00:00:00 to
23:59:59
‒‒
243.03 RlyTmr1Dur Duration for which the multifunction
relay remains activated for timer 1
in hh:mm:ss
00:00:00 to
99:59:00
‒‒
243.04 RlyTmr1Cyc Repetition cycle time for timer 1 Single Once Single
Daily Daily
Weekly Weekly
243.05 RlyTmr2StrDt Start date for timer 2 in dd.mm.yyyy ‒ ‒ 01.01.2011
243.06 RlyTmr2StrTm Start time at which the multifunction
relay activates for timer 2 in hh:mm:ss
00:00:00 to
23:59:59
‒‒
243.07 RlyTmr2Dur Duration for which the multifunction
relay remains activated for timer 2
in hh:mm:ss
00:00:00 to
99:59:00
‒‒
243.08 RlyTmr2Cyc Repetition cycle time for timer 2 Single Once Single
Daily Daily
Weekly Weekly
No. Name Description Value Default
value