SMA Solar Technology AG 5 Operating the Sunny Island via Sunny Remote Control
Operating Manual SI60H-80H-BE-en-20 25
Status of the external energy source
Figure11: Status of the external energy source in standard mode (example)
Position Symbol Designation Explanation
A Active limiting values Electrical limiting values for the utility grid are active.
Electrical limits for the generator are active.
B Status of the generator Voltage and frequency of the generator are within the limiting
values set.
Voltage and frequency of the generator are outside of the limiting
values set.
The maximum reverse power in the generator has been exceeded.
Battery
Generator was requested due to state of charge.
Cycle
Generator was requested via time control.
Extern
Generator was requested by an extension cluster.
Load
Generator was requested due to load.
Start
You have manually started the generator via Sunny Remote Control
or a generator was requested via the DigIn input.
Time
You have started the generator for one hour via Sunny Remote
Control.
C ‒ Power of the generator or
the utility grid
Power in kW
D Generator Generator symbol
E Internal transfer relay The generator is disconnected from the stand-alone grid.
The stand-alone grid is synchronized with the generator. The
generator is supplying the loads and charging the battery.