EasyManua.ls Logo

SMA SUNNY ISLAND 6.0H - Overvoltage and Overfrequency Errors; Derate and DerateSlv Errors

SMA SUNNY ISLAND 6.0H
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 Troubleshooting SMA Solar Technology AG
46 SI60H-80H-BE-en-20 Operating Manual
F 121 InvVtgHi 3 An overvoltage has occurred at
terminal AC1 of the master.
Ensure that the Sunny Island is
functional. For this, disconnect all
AC sources and loads from the
Sunny Island and restart the
Sunny Island.
Find the cause of the overvoltage
through measurement and
step-for-step connection of the AC
sources and loads.
W 122 InvVtgHiSlv1 1 An overvoltage has occurred at
terminal AC1 of slave 1.
W 123 InvVtgHiSlv2 1 An overvoltage has occurred at
terminal AC1 of slave 2.
F 129 InvFrqHi 3 An overfrequency has occurred at
terminal AC1 of the master.
Ensure that the Sunny Island is
functional. For this, disconnect all
AC sources and loads from the
Sunny Island and restart the
Sunny Island.
Find the cause of the
overfrequency through
measurement and step-by-step
connection of the AC sources and
loads.
W 130 InvFrqHiSlv1 1 An overfrequency has occurred at
terminal AC1 of slave 1.
W 131 InvFrqHiSlv2 1 An overfrequency has occurred at
terminal AC1 of slave 2.
F 133 InvFrqLo 3 An underfrequency has occurred
at terminal AC1 of the master.
Ensure that the Sunny Island is
functional. For this, disconnect all
AC sources and loads from the
Sunny Island and restart the
Sunny Island.
Find the cause of the
underfrequency through
measurement and step-by-step
connection of the AC sources and
loads.
W 134 InvFrqLoSlv1 1 An underfrequency has occurred
at terminal AC1 of slave 1.
W 135 InvFrqLoSlv2 1 An underfrequency has occurred
at terminal AC1 of slave 2.
W 137 Derate 1 The master has reduced the battery
charging current due to
overtemperature in the Sunny
Island.
Clean the fans (see Section10.7
"Cleaning the Fans", page75).
Reduce the total power of the
loads, e.g. by staggering their use
over time.
If the Sunny Island frequently
reduces its power, increase power
by replacing the Sunny Island with
a higher-powered version or by
installing additional Sunny Island
inverters.
W 138 DerateSlv1 1 Slave 1 has reduced the battery
charging current due to
overtemperature in the Sunny
Island.
W 139 DerateSlv2 1 Slave 2 has reduced the battery
charging current due to
overtemperature in the Sunny
Island.
No. Name Level Cause Corrective measures

Table of Contents

Other manuals for SMA SUNNY ISLAND 6.0H