SMA Solar Technology AG 9 Troubleshooting
Operating Manual SI60H-80H-BE-en-20 47
F 141 InvVtgLo 2 The voltage at terminal AC1 of the
master is too low due to AC
sources in the system.
Ensure that the Sunny Island is
functional. For this, disconnect all
AC sources and loads from the
Sunny Island and restart the
Sunny Island.
Find the cause of the undervoltage
through measurement and
step-by-step connection of the AC
sources and loads.
W 142 InvVtgLoSlv1 1 The voltage at terminal AC1 of
slave 1 is too low due to AC
sources in the system.
W 143 InvVtgLoSlv2 1 The voltage at terminal AC1 of
slave 2 is too low due to AC
sources in the system.
F 158 VtgOnAC1Det 2 The master has measured an
undesired voltage at terminal
AC1.
A bypass switch may have bridged the
internal transfer relay.
Ensure that the bypass switch is in
the position for operation with the
Sunny Island.
Ensure that the Sunny Island is
functional. For this, disconnect all
AC sources and loads from the
Sunny Island and restart the
Sunny Island.
A voltage source (e.g. generator) may
have been connected to the terminal
AC1.
Disconnect the voltage source
from terminal AC1 and connect to
terminal AC2 (see the Sunny
Island installation manual).
W 159 VtgOnAC1DetSlv1 1 Slave 1 has measured an
undesired voltage at terminal
AC1.
W 160 VtgOnAC1DetSlv2 1 Slave 2 has measured an
undesired voltage at terminal
AC1.
F 162 OvrCurDet 2 Too much current is flowing
through the DC terminal of the
master.
Reduce the power of the loads.
W 163 OvrCurDetSlv1 1 Too much current is flowing
through the DC terminal of slave 1.
W 164 OvrCurDetSlv2 1 Too much current is flowing
through the DC terminal of slave 2.
F 166 Overload5min 3 The five minute overload capacity
of the master has been exceeded.
Reduce the power of the loads.
W 167 Overload5minSlv1 1 The five minute overload capacity
of slave 1 has been exceeded.
W 168 Overload5minSlv2 1 The five minute overload capacity
of slave 2 has been exceeded.
No. Name Level Cause Corrective measures