Chapter 5 Display and Setting of Various Functions
5.4 Description of the Screen
HRS Series
5-38
Table 5.4-8 Settings for AL18/AL19/AL20
No.
Indication
Item
Setting and selection
Setting range
(1)
High
Press.
AL19 :
Circulating
fluid discharge
pressure rise
Disabled
0.03 to 0.68MPa
0.50MPa
Operation continues
during the alarm
Operation stops during
alarm
(2)
Low
Press.
AL20 :
Circulating
fluid discharge
pressure drop
Disabled
0.03 to 0.68MPa
0.03MPa
Operation continues
during the alarm
Operation stops during
alarm
(3)
Press.
Sensor
Alarm
AL18: Failure
of circulating
fluid discharge
pressure sensor
Disabled
Operation continues
during the alarm
Operation stops during
alarm
By default
Setting of discharge pressure alarm
(AL18/AL19/AL20)
(1)
(2)
(3)