DOC1001322
Chapter 8 Documents
HRS Series 8.1 Specifications
8-1
Chapter 8 Documents
8.1 Specifications
8.1.1 HRS400-A-46-
Table 8.1-1 Specifications
Model
HRS400-A-46-
Cooling method
Air-cooled refrigeration
Refrigerant
R410A(HFC)
Quantity of refrigerant
kg
3.7
Control method
PID control
Ambient temperature 1
°C
-5 to 45
Circulating
fluid
system
Circulating fluid 1 2
Clean water, 15% ethylene glycol aqueous solution, Deionized water
Set temperature range 1
°C
5 to 35
Cooling capacity 3
kW
38
Heating capacity 4
kW
8
Temperature stability 5
°C
±0.1
Pump
capacity
Rated flow rate
(Outlet)
L/min
125
(0.45MPa)
Maximum flow
rate
L/min
180
Maximum lifting
height
m
68
Settable pressure range 6
MPa
0.10 to 0.68
Minimum operating flow rate 7
L/min
40
Tank capacity
L
60
Electric conductivity setting range 8
μS/cm
0.5 to 45
Circulating fluid outlet,
Circulating fluid return port
Rc1 (Symbol F: G1,Symbol N: NPT1)
Tank drain port
Rc3/4 (Symbol F: G3/4,Symbol N: NPT3/4
Automatic
fluid fill
function
(Standard)
Supply side pressure
range
MPa
0.2 to 0.5
Supply side fluid temp.
range
5 to 35
Automatic fluid fill port size
Rc1/2 (Symbol F: G1/2, Symbol N: NPT1/2)
Over flow port size
Rc1 (Symbol F: G1, Symbol N: NPT1)
Wetted material
Stainless steel, Copper (Brazing filler metal for the heat exchanger) 9,
Brass 9, Bronze 9, PTFE 9, PU 9, FKM, EPDM, PVC, NBR ,
PE, POM, NR 9, PBT 9,
Aluminum oxide ceramic 10, SiC 10, Carbon 10, PP 10
Electrical
system
Power supply
3-phase 380 to 415VAC(50/60Hz)
Allowable voltage range ±10%(No continuous voltage fluctuation)
3-phase 460 to 480VAC(60Hz)
Allowable voltage range +4%,-10%(Max. voltage less than 500V and no
continuous voltage fluctuation)
Applicable earth
leakage breaker
Rated
current
A
40
Sensitivity
current
mA
30
Rated operating current 5
A
22
Rated power consumption 5
kW
(kVA)
14.3(15.2)
Noise level (Front: 1m, height: 1m) 5
dB(A)
71
Accessories
Operation manual (for installation/operation) (English 1, Japanese 1)
Y strainer (40 mesh) 25A, Barrel nipple 25A,
Anchor bracket 2pcs. (including 6 pcs. of M8 bolts)
11
Weight
(in the dry state) 12
kg
Approx.340
1 When the ambient temperature or circulating fluid temperature is 10
o
C or below, refer to "3.2.2 Operation at low ambient temperature or low
circulating fluid temperature".
2 Use fluid for circulating fluid that conforms to:
Clean water: Water Quality Standards of the Japan Refrigeration and Air Conditioning Industry Association (JRA GL-02-1994)
15% ethylene glycol aqueous solution: Diluted with clean water, without any additives such as antiseptics.
DI water (pure water): Electrical conductivity 1 μS/cm or more (electrical resistivity 1MΩcm or less)
3 (1) Ambient temperature: 32
o
C, (2) Circulating fluid: Clean water, (3) Circulating fluid temperature: 20
o
C, (4) Circulating fluid flow rate: Rated flow
rate, (5) Power supply: 400 VAC
4 (1) Ambient temperature: 32
o
C, (2) Circulating fluid: Clean water, (3) Circulating fluid flow rate: Rated flow rate
(4) Power supply: 400 VAC
5 (1) Ambient temperature: 32
o
C, (2) Circulating fluid: Clean water, (3) Circulating fluid temperature: 20
o
C, (4) Load: Refer to the cooling capacity
shown in the specification table, (5) Circulating fluid flow rate: Rated flow rate, (6) Power supply: 400 VAC, (7) Piping length: Minimum
6 With the pressure control mode that controls the pressure automatically with the inverter.If the pressure control mode is not
necessary,use the flow control function or the pump output setting function.