Chapter 5 Display and Setting of Various Functions
5.4 Description of the Screen
HRS Series
5-54
Setting of contact input signal form
4. The type and form of contact input signal are set. Following items can be set for contact input
signal 1 and 2:
Contact type…selects [ ] (A contact) or [ ] (B contact)
Signal formselects [ ] (alternate) or [ ] (momentary)
Signal type…selects “OFF” (disabled), “External switch” (external switch signal) or
“Run/Stop” (run/stop) signal.
“Operation mode” can be switched from “Local mode/Serial mode” to “DIO mode” by inputting
a contact signal in contact input 3. Refer to the “Communication Function” of Operation
Manual for details.
Table 5.4-21 Setting of contact input signal form
No.
Indication
Item
Setting and selection
(1)
Input 1
Contact input
signal 1
Contact
type
1
A contact (normally open)
B contact
(normally closed)
Signal
form
1
Alternate
Momentary
Signal
type
[Off]
Disabled
[External Switch]
External switch signal
[Run/Stop] 1
Run/stop signal
[Run] 2
Run signal
(2)
Input 2
Contact input
signal 2
Contact
type
1
A contact (normally open)
B contact
(normally closed)
Signal
form
1
Alternate
Momentary
Signal
type
[Off]
Disabled
[External Switch] 1
External switch signal
[Stop] 2
Stop signal
(3)
Input 3
Contact input
signal 3 3
Contact
type
1
A contact (normally open)
B contact
(normally closed)
1 By default.
2 This setting assigns “Runsignal to “Contact input 1” and Stopsignal to “Contact input 2”.
3 The signal form of contact input 3 is “Momentary”.
Setting of contact input signal form
(1)
(2)
(3)