Chapter 5 Display and Setting of Various Functions
HRS Series 5.4 Description of the Screen
5-47
TEMP OUT signal
4. Set “TEMP OUT” signal.
“TEMP OUT” signal has a function to make an arbitrary selection from the following six
alarm signals to output a “TEMP OUT” signal from a contact or serial communication.
This function is set to “OFFˮ (disabled) by default.
Table 5.4-15 Settings for TEMP OUT signal
No.
Indication
Explanation
Setting
(1)
High Temp.
Alarm
Alarm “AL10: circulating fluid
temperature rise”
Disabled
Enabled
(2)
Low Temp.
Alarm
Alarm “AL11: circulating fluid
temperature drop”
Disabled
Enabled
(3)
TEMP READY
Alarm
Alarm “AL12: TEMP READY alarm”
Disabled
Enabled
By default
TEMP OUT signal output chart
(1) Alarm “AL10: Circulating fluid
temperature rise”
(2) Alarm “AL11: Circulating fluid
temperature drop
(3) Alarm “AL12: TEMP READY alarm”
“TEMP OUT
signal
Alarm signal
Select
ON/OFF
ON/OFF
ON/OFF
Setting screen of TEMP OUT signal
(1)
(2)
(3)