Table 5.4-7 Pump operation mode setting
By default
・Discharge pressure alarm (AL18/AL19/AL20)
5. An alarm can be activated when the circulating fluid discharge pressure rises/drops outside
the setting range.This function is set to “ [ ] (stop) at the time of alarm” by default.
The following two alarms can be set on “Discharge pressure alarm setting” screen:
• AL19: Alarm for circulating fluid discharge pressure rise––this alarm activates when
the pressure rises above the set pressure.
• AL20: Alarm for circulating fluid discharge pressure drop––this alarm activates
when the pressure drops below the set pressure.
Following settings can also be selected:
• Selection of product operation when an alarm occurs
The alarm “AL18: failure of circulating fluid discharge pressure sensor” activates
when a failure is detected in the circulating fluid discharge pressure sensor. This allows
selecting the product operation when the alarm “AL18” is activated.
This function is set to “Operation stops at time of alarm” by default.
If the operation at the time of the alarm “AL18” is set to become [ ] (disabled) or
[ ] (operation continues at time of alarm), the pump operation mode switches to
the “Pump output setting modeˮ (50% output) to continue operation when a pressure
sensor failure is detected.