Chapter 5 Display and Setting of Various Functions
HRS Series 5.4 Description of the Screen
5-43
Table 5.4-10 Settings of key-lock, startup operation, anti-freezing and warming-up
No.
Indication
Item
Explanation
Setting range
(1)
KEY LOCK
Key-lock
Disabled
Enabled
(2)
START-UP
Startup
operation
Disabled
Enabled
(3)
ANTI-
FREEZE
Anti-freezing
Disabled
Enabled
(4)
WARMING
UP
Warming-up
Disabled
Enabled
TEMP SP
Set temperature
5.0 to 35.0 ºC
5.0 ºC
By default
Continuing pump operation
2. Continuing pump operation can be set.
Refer to “■ About continuous pump operation function” (P.5-44) for this function.
This function is set to “Disabled” by default.
Following items can be set on “Continuous pump operation” setting screen:
Pump operation sustainable temperature
Pump operation sustainable time
Table 5.4-11 Settings for continuous pump operation
No.
Indication
Item
Explanation
Setting range
(1)
Temp. Limit
Pump operation
sustainable
temperature
“Continuous pump operationends
when the temperature reaches the
set temperature.
5.0 to 50.0 ºC
45.0 ºC
(2)
Time
Pump operation
sustainable time
“Continuous pump operationends
when the set time has elapsed.
Set time: 0 sec––this function is
“Disabled”
0 to 9999sec
0sec
By default
Setting for continuous pump operation
(1)
(2)

Table of Contents