DOC1001322
Chapter 5 Display and Setting of Various Functions
5.4 Description of the Screen
HRS Series
5-44
About continuous pump operation function
This function allows just the pump to continue operating after some alarms are activated.
Alarms that allow continuous pump operation are shown in Table 5.4-12 Alarms that allow
continuous pump operation (1/2) and Table 5.4-13 Alarms that allow continuous pump operation
(2/2).
“Continuous pump operationends if any one of the following conditions is met, and the product
stops operating:
(1) After activation of the alarm, the temperature has reached the “Pump operation sustainable
temperaturefrom the temperature at which pump-only operation starts.
(2) After activation of the alarm, the time reached the “Pump operation sustainable time” starting
from the time at which pump-only-operation started
Table 5.4-12 Alarms that allow continuous pump operation (1/2)
Alarm No.
Alarm name
Alarms that allow
continuous pump operation
Operation
AL01
Low Level FLT
[FLT]
×
AL02
Low Level WRN
[WRN]
AL06
Fan Inverter
[FLT]
AL09
High Temp. FLT
[FLT]
×
AL10
High Temp.
[OFF]/ [WRN]
-
[FLT]
AL11
Low Temp.
[OFF]/ [WRN]
-
[FLT]
AL12
TEMP READY ALARM
[OFF]/[WRN]
-
[FLT]
AL17
HX In High Temp. FLT
[FLT]
×
AL18
Press. Sensor
[OFF] / [WRN]
-
[FLT]
×
AL19
High Press.
[OFF] / [WRN]
-
[FLT]
×
AL20
Low Press.
[OFF] / [WRN]
-
[FLT]
Default setting.