SMC Networks HRS Series - Setting of Contact Output Signal 1 to 3

SMC Networks HRS Series
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DOC1001322
Chapter 5 Display and Setting of Various Functions
HRS Series 5.4 Description of the Screen
5-55
Setting of contact output signal 1 to 3
5. Set contact output signal 1 to 3. Contact output signal is continuously output.
The signal type of contact output signal 1 to 3 is fixed. Contact output signal 4 to 6 can be
used to change the signal type. The contact type of the following contact output signals can be
set:
Contact output signal 1 “Operation status” –– selects “N.O.” (A contact) or “N.C.” (B contact).
Contact output signal 2 “FLT alarm” –––––––selects “N.O.” (A contact) or “N.C.” (B contact).
Contact output signal 3 “WRN alarm” ––––––selects “N.O.” (A contact) or “N.C.” (B contact).
Table 5.4-22 Setting of contact output signal 1 to 3
No.
Indication
Item
Setting and selection
(1)
Output 1
Contact output
signal 1
Operation status
signal
A contact
(normally open)
B contact
(normally closed)
(2)
Output 2
Contact output
signal 2
Operation stop
(FLT) alarm status
signal
A contact
(normally open)
B contact
(normally closed)
(3)
Output 3
Contact output
signal 3
Continuous
operation “WRN
alarm status signal
A contact
(normally open)
B contact
(normally closed)
By default
Setting of contact output signal 4 to 6
6. Set contact output signal 4 to 6. Contact output signal is continuously output.
A “Signal type” for contact output signal 4 to 6 can be selected by the customer. Refer to
Table 5.4-24 Signal type for contact output signals 4 to 6.“
Select the “Contact type” and “Signal type” for contact output signals 4 to 6.
Contact output signal 4––selects “Signal type” and “N.O.” (A contact ) or “N.C.” (B contact).
Contact output signal 5––selects “Signal type” and “N.O.” (A contact ) or “N.C.” (B contact).
Contact output signal 6––selects “Signal type” and “N.O.” (A contact) or “N.C.” (B contact).
(1)
(2)
(3)
Setting of contact output signal 1 to 3