Chapter 6 Alarm Notifications and Troubleshooting
HRL Series 6.3 Troubleshooting
6-3
Table 6.3-1 Alarm codes and troubleshooting (1/2)
Sub code Operation Threshold
AL01
FLT
AL02 WRN
AL06 FLT
Check that there is no abnormality
with the power supply system
(e.g. ground fault, short-circuit, voltage
fluctuation,abnormal interphase voltage,
open phase, surge).
AL09 FLT 55ºC
AL10 OFF 1 45ºC 3
AL20 FLT 1 0.03MPa 3 Restart the thermo-chiller and check if the pump runs.
AL28 4 WRN 2 45.0μS/cm 3 Replace DI filter.
AL29 FLT
Shut off the power to this product and restart it without
connecting usb port.
AL30 FLT 1
AL31 FLT 1
AL34
Communication
WRN 1
No request message from the host computer.
Try to send the request message again.
AL35
Ambient Temp.
OFF 2
2ºC/45ºC
Check the environment.
Low Press.
High Electric conductivity
No Power Supply
Digital input 1
Contact input has been detected.
Digital input 2
AL18
Press. Sensor
FLT 1
Short-circuit or broken wire of the pressure
sensor.Ask for the service.
AL19
High Press.
FLT 1
0.50MPa 3
Check that there is no bending, collapse,
or clogging with the external piping.
AL12
TEMP READY ALARM
OFF 1
+1/-1ºC 3
There may be causes such as large
load fluctuation and flow rate fluctuation.
Please review the setting value.
AL17
HX In High Temp. FLT
FLT
60ºC
Check that the circulating fluid flow rate
is more than the minimum flow rate.
Check that the heat load is within
the specified range.
Fan Inverter
Hgih Temp. FLT
Check that the ambient temperature,
and heat load satisfy the specifications,
and that the circulating fluid flow rate is
more than the minimum flow rate.
Please review the setting value.
Hgih Temp.
AL11
Low Temp.
OFF 1
5ºC 3
Check the effect of ambient temperature.
Please review the setting value.
Alarm
code
Alarm content
Default setting
Cause/Countermeasure
(Please reset the alarm after eliminating the cause.)
Low Level FLT
The circulating fluid level has decreased.
Refilling circulating fluid.
Low Level WRN