Chapter 7 Control, Inspection and Cleaning
7.3 Operation Stop for an Extended Period of Time
HRL Series
4. 【For Option D】
Remove the DI filter.
1) Remove the maintenance panel and remove the DI filter.
(Refer to “7.4.1 Replacing the DI filter”.) Store the removed DI filter separately.
2) Install the DI filter temporary piping that was installed at the time of delivery.
Fig. 7-3 Temporary pipe installation for DI filter(For option D)
5. After confirming that the circulating fluid has been sufficiently discharged from the product,
customer's facilities and piping, perform an air purge (pressure less than 0.1 MPa, about 1
minute) from the circulating fluid outlet of the product.
Circulating fluid is drained from the drain port.
6. Close the ball valve after draining the circulating fluid.