Chapter 3 Transport and Setting Up
3.5 Circulating Fluid Supply
HRS Series
3-34
3. Supply the circulating fluid to the fluid fill port.
Please supply the circulating fluid to the fluid level between “HIGH” and
“LOW” levels of the fluid level gauge.
Fig. 3-21 supplying the fluid to the fluid fill port (An example)
Confirm that the valve of the drain port is closed to prevent the
supplied circulating fluid from draining out.
Confirm that the fluid level is between “HIGH” and “LOW” levels of the
fluid level gauge. If it exceeds the specified level, the circulating fluid
will overflow.
Be sure to connect the piping from the overflow port to the drainage
pit to drain the excessive amount of the fluid from the tank.