DOC1001322
Chapter 5 Display and Setting of Various Functions
HRS Series 5.4 Description of the Screen
Table 5.4-3 Screen display of check operation time screen
Displays the operating time for pump.
Displays the recommended replacement
cycle for pump.
Displays the operating time for compressor.
Displays the recommended replacement
cycle for a compressor.
Displays the operating time of a fan.
Displays the recommended replacement
cycle for a fan.
Displays the usage time of a DI filter.
1 to 9999 hour
By default: 500 hour
The “Maintenance reminder” is issued if the usage
time has reached the hours specified by the user.
Displays the usage time of a dustproof filter.
1 to 9999 hour
By default: 500 hour
The “Maintenance reminder” is issued if the usage
time has reached the hours specified by the user.
Displays the operation time of a chiller.
The operation time is reset to “0 hour” when
[ ] button is pressed.
1 In the case of option D "With electrical conductivity control", to display the value.
■About “Maintenance reminder” function
・“Maintenance reminder” is displayed on the “Informationˮ screen if a product part in use
has reached its recommended replacement cycle.
・“Maintenance reminder” is always issued if a part of the product has reached the
recommended replacement cycle.
・A “Maintenance reminder” signal can be output by contact signal and by serial
communication. Communication setting screen
(Refer to “5.4.9 Communication setting screen” for details.)
・A “Maintenance reminder” signal can be output as “The AL36: Maintenance alarm”.
(Refer to “5.4.8 Ambient temperature alarm [AL35] and Maintenance Alarm [AL36]”.)