■ About alarm monitoring timing
If [ ] is selected as (3) “Monitor Timing” alarm monitoring condition, [ ] and
[ ] can be additionally selected. [ ] is a function to start alarm monitoring when the
circulating fluid temperature rises/drops within the alarm setting temperature range in the
time period specified by (4) “Start Time” (no monitoring time). Specific alarm monitoring
timing is shown in “Figure 5-5 Alarm monitoring timing”.
[Example of setting]
• Circulating fluid SP: 20ºC
• (1) “High Temp.” Circulating fluid temperature rise (AL10): 22ºC
• (2) “Low Temp.” Circulating fluid temperature drop (AL11): 18ºC
• (3) “Monitor Timing” Alarm monitoring conditions: [ ] and [ ]
• (4) “Start Time” No monitoring time: 1200 sec / “Out Time” : 600 sec