Chapter 5 Display and Setting of Various Functions
HRS Series 5.4 Description of the Screen
5-29
About alarm monitoring timing
If [ ] is selected as (3) “Monitor Timingalarm monitoring condition, [ ] and
[ ] can be additionally selected. [ ] is a function to start alarm monitoring when the
circulating fluid temperature rises/drops within the alarm setting temperature range in the
time period specified by (4) “Start Time(no monitoring time). Specific alarm monitoring
timing is shown in “Figure 5-5 Alarm monitoring timing”.
[Example of setting]
Circulating fluid SP: 20ºC
(1) “High Temp.Circulating fluid temperature rise (AL10): 22ºC
(2) “Low Temp.Circulating fluid temperature drop (AL11): 18ºC
(3) “Monitor TimingAlarm monitoring conditions: [ ] and [ ]
(4) “Start TimeNo monitoring time: 1200 sec / “Out Time” : 600 sec
Time
Chiller
Operation
Stop
Circulating fluid set
temperature 20ºC
AL10 alarm monitoring
ON
OFF
(2)
Alarm AL10
Generate
No alarm
AL10 set
temperature 22°C
400sec
500sec
(3)
(4)
600sec
(5)
Circulating fluid
temperature
(1)
AL11 alarm monitoring
ON
OFF
1200sec
Alarm AL11
Generate
No alarm
AL11 set
temperature 18°C
Fig. 5-5 Alarm monitoring timing