Chapter 5 Display and Setting of Various Functions
HRS Series 5.4 Description of the Screen
5-35
Example of MODE 2
When the offset temperature is -1
o
C, circulating fluid display temperature and the communication data is
29
o
C (circulating fluid discharge temperature + offset temperature), and matches the circulating fluid
temperature at the customer's device.
Example of MODE 3
When the offset temperature is 1
o
C, the thermo-chiller controls the temperature at 31
o
C (circulating fluid
set temperature + offset temperature) Even if the discharge temperature is 31
o
C, the circulating fluid
temperature is 30
o
C at the customer’s device because of 1
o
C of heat radiation during sending of the fluid.
The circulating fluid display temperature and the communication data is 30
o
C (circulating fluid discharge
temp. - offset temp.), and matches the circulating fluid temperature at the customer's device.
Circulating fluid display
temperature
29
Circulating fluid set
temperature
30
Offset temperature
-1
This produuct Your system
Serial communication
Discharge
temperature 30
29℃
Circulating fluid
temperature 29
Heat
radiation
1
Circulating fluid display
temperature
30
Circulating fluid set
temperature
30
Offset temperature
1
This produuct Your system
Serial communication
Discharge
temperature 31
30℃
Circulating fluid
temperature 30
Heat
radiation
1