10.1.2.3. Conguration of the insulation
ISOM L-60
The "Common" screen denes the general settings of the device:
1) the network prole:
Choosing the prole is an easy way to support the measurement algorithm on the intended application, with
improved ltering/measurement times.
You can choose between 3 proles:
• Custom
• Cabinet
• Control/command
2) The booster startup mode for nding the fault:
• Automatic: start the "LCI" booster when the "ALARM 2" threshold is reached
• Manual: start up the "LCI" booster only with the BP "INJ START/STOP"
3) Manual test input:
Denes which ON/OFF input (1 to 4) on the device is used to carry out a remote internal test of the device.
4) Operating mode of the relays:
Denes if these relays are active or stopped.