Chapter 7 Parameter Explanation
Shanghai Sigriner STEP Electric Co., Ltd.
- 102 -
PID main preset switching to
analog A1
PID auxiliary preset switching
to analog A1
Velocity channel switching
Control mode switching 0
(Standby)
Control mode switching 1
(Standby)
Control mode switching 2
(Standby)
Motor vibration signal
(Standby)
Trickle heating (Standby)
Reverse de-icing (Standby)
0: No function
1: Acceleration and deceleration selection 0
2: Acceleration and deceleration selection 1
See the following table for instructions on usage:
Acceleration and
deceleration velocity
option 1
Acceleration and
deceleration velocity
option 0
Acceleration and deceleration time
option
Acceleration and deceleration time 0
(P40.02, P40.03)
Acceleration and deceleration time 1
(P40.04, P40.05)
Acceleration and deceleration time 2
(P40.06, P40.07)
Acceleration and deceleration time 3
(P40.08, P40.09)
3: Digital segment speed 0
4: Digital segment speed 1
5: Digital segment speed 2
6: Digital segment speed 3
See P41.00 - P41.15 for instructions on usage
7: Terminal forward input (FWD)
8: Terminal reverse input (REV)
9: 3-wire operation control
It is valid only when the terminal running command is used (P10.02=1). See P10.01 for instructions
on usage.
11: Variable frequency to power frequency
When this signal is valid, it switches from variable frequency drive to grid direct drive.
13: External reset terminal
The external reset terminal signal is valid, and the external signal resets the fault of the inverter.
14: External fault terminal
The external fault terminal signal is valid, and the inverter stops running.
17: Weighing compensation input (spare)
Command input for weighing compensation set by the user for a specific application.