Chapter 4 Wiring of Inverter
ET/EP/EH Series Intelligent Flexible Driver Manual
- 39 -
Wire cross-sectional area (mm
2
)
Terminal screw specifications
Specifications for round crimp
terminals
Important
When determining the cross-sectional area of the wire, give due consideration to the voltage drop of
the wire.
The general selection principle is to keep the voltage change within 2% of the rated voltage. When
the voltage drop is too much, the cross-sectional area of the wire should be increased. The formula
for calculating the voltage drop is as follows:
Voltage drop between lines (V) =
* wire resistance (Ω) * current (A)
4.3.4 Description on main circuit terminal wiring
4.3.4.1 Power supply
The inverter must be connected to a protective earth. Considering the high leakage current (over
3.5mA), a protective earth must be used in order to comply with the relevant current regulations.