Chapter 7 Parameter Explanation
Shanghai Sigriner STEP Electric Co., Ltd.
- 82 -
Function code area
Domain group
number
Function code description
P96 group
Inverter information
7.2 Group P0X User parameters group
7.2.1 P00 Group Basic function parameters
Function code
Name
Setting range
Factory setting
P00.00
Login password
0~65535
0
This function is used to prevent irrelevant personnel from querying and modifying parameters and
protect the security of inverter parameters.
00000: No password protection, and all parameters can be queried; and there is no factory password
of the inverter.
Once the user password setting takes effect, when entering the parameter setting state again, all the
parameters will not be modified through the operation panel and they can only be viewed, unless the
user enters the correct password. The password in the parameter is always shown as 00000.
Note: The factory setting of the intelligent flexible driver is no user password (P00.00 = 0), therefore,
no password is required to log in for the first use.
Function code
Name
Setting range
Factory setting
P00.01
Modify password
0~65535
0
Set password:
Enter 5 digits as user password; press ENTER to confirm, and repeat setting again.
Modify password:
Press ENTER to enter the password verification state in which 00000 is displayed. Enter the correct
password and enter the parameter editing state. Select P00.01 (P00.00 parameter is displayed as
00000), enter the new password and press ENTER to confirm; repeat the password setting with the
same password for P00.01 to successfully complete the new password setting after the screen
displays "Password Setting Successfully".
Cancel password:
Press ENTER to enter the password verification status in which 00000 is displayed; enter the correct
user password and enter the parameter editing state. Check P00.01 is 00000, and press ENTER to
confirm; and repeat setting of P00.01 = 00000 to clear the password after the screen displays
"Password Clear".
7.3 Group P1X Control parameter group
7.3.1 Group P10 Basic control parameters
Function code
Name
Setting range
Factory setting
P10.00
Control mode selection
0~6
0
This function is used to set the control operation mode of the inverter.
0: GVC control applies to most applications, adapting to synchronous motors, asynchronous motors,
and reluctance motors. This control mode mainly corresponds to P17 group parameters.
1: No PG vector control without sensor vector control, adapting to synchronous motors and
asynchronous motors.
2: PG torque control, supporting ABZ encoder, SINCOS encoder, and Rezav encoder.