Chapter 5 Debugging and Test
Run
Shanghai Sigriner STEP Electric Co., Ltd.
- 56 -
Description: enter the monitoring state after displaying the software version number.
5.3.2 Display after power-on
The "Monitoring Status" interface is displayed after power on for 2 seconds. This interface displays
by default the current recorded target speed, preset speed, feedback speed, and output current.
5.3.3 [Monitor Status] Details
Entering the monitoring settings to select standard monitoring or waveform monitoring. 8 displays
can be set by standard monitoring.
Table 5.1 Default running status data comparison
Name
Description
Setting
range
Unit
Factory
setting
Remarks
Target speed
Display the target speed command
value of the motor
×
Hz
×
Setting speed
Display the speed setting command
value of the motor
×
Hz
×
Feedback
speed
Display the speed value of the motor
feedback
×
Hz
×
Output
current
Display output current
×
A
×
Output
voltage
Display the output value
×
V
×
Bus voltage
Display the DC voltage of the main
circuit inside the inverter
×
V
×
Output power
Display output power
×
kW
×
Output
torque
Display the torque output value
×
%
×
Input X0-X6
status
Display the status of input terminals
X0-X6. DI is displayed in
"XXXXXXXX” format, where "x" =
0, indicating no input; "X" = 1,
indicating input.
×
×
×
Status of
output
K1-K2, Y0
andY1
Display the status of output
terminals K1-K2, Y0 and Y1. DO is
displayed in "XXXXXX” format,
where "x" = 0, indicating no output;
"X" = 1, indicating output.
×
×
×
5.3.4 Detailed description of [Panel Control]
Press to switch between the “Monitoring Status” and “Panel Control” two statues. In the
“Panel Control” status, press can control the inverter to enter the running status, and press
to control the inverter to enter the stopping status. In the “Panel Control” interface, press
and keys to switch the monitored content, and the running frequency can be set via
”, or ”.