EasyManua.ls Logo

STEP ET Series - Connection of Main Circuit Peripheral Devices

Default Icon
200 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Wiring of Inverter
Shanghai Sigriner STEP Electric Co., Ltd.
- 32 -
4.1.2 Connection of main circuit peripheral devices
4.1.2.1 Input power connection
The inverter cannot be operated outside the rated input line voltage range; overvoltage may
cause permanent damage to the inverter.
Table 4-1 Technical requirements for input power
Technical requirements for input power (main circuit) connection
Input voltage
Voltage is three-phase 380~480VAC, -15%~+10%
Short-circuit current
(IEC60909 standard)
If the incoming cable of the inverter is protected by a suitable fuse, then the
maximum allowable short-circuit current is 100kA within 1s
Frequency
50~60Hz, -5%~+5%
Unbalance degree
Maximum ±3% of rated input line voltage
Cable temperature
Min. rated value: 90°C
4.1.2.2 Input protection
Input protection includes circuit breakers, fuses, emergency stop devices, etc.
Circuit breaker
The inverter itself does not include disconnection device. Therefore, a disconnection device must be
installed between the AC input power and the inverter. This disconnection device must conform to
the following requirements:
The device shall comply with safety regulations of the actual application, including (but
not limited to) national and local electrical regulations.
The disconnection device must stay in the off position and locked out during installation
and maintenance of the inverter.
The disconnection device should not be used to control the start/stop of the motor. The
motor should be controlled using the operator keys, or commands from the I/O terminals.
The capacity of the circuit breaker should be selected as 1.5 to 2 times the rated current of
the inverter.
The time characteristics of the circuit breaker should take full account of the time
characteristics of the inverter overheating protection (150% of the rated output current for
1 min).
Fuse
The end user must provide a circuit protection device and the device should be selected in
accordance with national and local electrical regulations. Table 4-2 provides the recommended fuse
types to offer short circuit protection for the incoming power section of the inverter.
Table 4-2 Recommended fuse models (the recommended fuse Bussmann meets UL certification)
Inverter
model
EP6/ET6
inverter
capacity
(kW)
EH6
inverter
capacity
(kW)
Main fuse
Model
4T4A1
1.1
1.5
10
FWP-10B
4T5A6
1.5
2.2
15
FWP-15B
4T7A2
2.2
3
15
FWP-15B
4T9A4
3
4
20
FWP-20B
4T012
4
5.5
30
FWP-30B
4T018
5.5
7.5
40
FWP-40B

Table of Contents