Chapter 7 Parameter Explanation
Shanghai Sigriner STEP Electric Co., Ltd.
- 126 -
direction can be set, 0 indicates forward direction and 1 indicates reverse direction; by setting P62.02
and P62.03, torque acceleration and deceleration rate can be set.
Function code
Name
Setting range
Factory setting
P63.00
Compensating torque direction
0~1
0
P63.01
Compensation torque gain (%)
0~6553.5
100.0
P63.03
Preset torque compensation (%)
0.0~6344.0
0.0
This parameter group is used mainly in applications requiring compensating fixed torque.
7.9 P7X group Enhanced control
7.9.1 P70 group Limit and protection
Function code
Name
Setting range
Factory setting
P70.00
Frequency upper limit(Hz)
0.00~655.35
50.00
P70.01
Frequency lower limit (Hz)
0.00~655.35
0.00
The maximum output frequency f
max
is the highest frequency allowed to be output by the inverter.
The maximum output voltage Vmax is the output voltage of the inverter when it runs at the basic
operating frequency, which corresponds to the rated voltage of the motor when using a standard AC
motor. See the motor nameplate.
The upper frequency limit f
H
and lower frequency limit f
L
are the maximum and minimum
frequencies of motor operation set by the user according to the requirements of the production
process.
Figure 7 - 32 Diagram of frequency upper and lower limits
Function code
Name
Setting range
Factory setting
P70.02
ID preset limit
0.00~2.00
0.00
P70.03
ID limit gain
0~10000
0
P70.02 is the D axis current preset limiting value. Exceeding this value will enter the speed reduction
control.
P70.03 is the ID limiting gain, which determines amplitude value of the speed reduction.
Function code
Name
Setting range
Factory setting
P70.04
Output torque limit (%)
0~250
150
P70.05
Accelerated overcurrent
threshold (%)
0~200
160
P70.06
Decelerated overvoltage
540~800
750
Output voltage
Output
frequency