Chapter 4 Wiring of Inverter
Shanghai Sigriner STEP Electric Co., Ltd.
- 12 -
EP6/ET6 series (heavy load)
Remarks: 1. The DC reactor is equipped in the EP6 series ≥ 22 kW as standard
configuration;
2. The DC reactor is equipped in the EH6 series ≥ 30 kW as standard configuration;
3. The DC reactor is equipped in the ET6 series full range as standard configuration.
2.2 Technical performance and specifications of the inverter
380-480 V (-15% - +10%), three-phased TN, TT
Allowable
voltage
fluctuation
Heavy load 150%, 1 min/10min; light load 110%, 1 min/10min
1.5-16 kHz (derated); the carrier frequency can be automatically adjusted
according to load features.
(Derating is required for the use above the rated carrier frequency)
Frequency
setting resolution
Digital input: 0.01 Hz
Analog input: 1/2048 of the highest output frequency (signed 11 bits)
Operation panel setting, control terminal setting, communication setting
Operation panel preset, digital/analog preset, communication preset, pulse
preset
Automatically adjusts the duty cycle of the output PWM signal according to
the fluctuation of bus voltage, thus reducing the impact of grid voltage