Chapter 4 Wiring of Inverter
ET/EP/EH Series Intelligent Flexible Driver Manual
- 13 -
fluctuation on output voltage fluctuation
Energy
consumption
braking capacity
EH6 series: This series are not equipped with the brake unit.
EP6 series: The brake unit is equipped in HD ≤ 30 kW (standard);
EH6 series: The built-in brake unit is equipped in HD ≤ 75kW (standard), the
external brake uint is equipped in HD 90kW
Vertically installed in a well-ventilated electrical control cabinet. Horizontal
or other mounting is not allowed. Cooling medium is air. Installed in an
environment free from direct sunlight, dust, corrosive gas, combustible gas,
oil mist, steam and dripping water
Intra-cabinet-mounted type (IP20): heavy load -10 ° C - +50 ° C
Light load -10°C - +40°C
The rated output current decreases by 1% per 1 ℃ increase of upper limit
temperature
Heavy load up to 60 ℃, light load up to 50 ℃
In case of >1000 meters, the rated output current decreases by 1% per 100
meters of elevation, up to 2,000 meters
5~95%, no condensation allowed
Vibration
(transportation)
2≤ f
<
9 Hz, 3.5 mm; 9 ≤f
<
200 Hz, 10 m/s2; 200 ≤ f
<
500 Hz, 15 m/s2
2≤ F
<
9, 0.3 mm; 9 ≤ f
<
200 Hz, 1 m/s2
1m (length can be customized, maximum 3m)
14 * 14 Chinese characters or letters, with 8 rows in total and 17 characters
per row
Intra-cabinet wall mounted type