Chapter 4 Wiring of Inverter
Shanghai Sigriner STEP Electric Co., Ltd.
- 38 -
Terminal function description
Grounding terminal, connected to the protection ground, ground
resistance can not be greater than 1Ω at 400V class
4.3.3 The wire specifications of main circuit wiring
The conductor uses 600V copper-core plastic insulated wire or similar wires for power supply. Wire
specifications and tightening torque are shown in Table 4-11.
Table 4-11 Wire specifications and tightening torque
Inverter model
Intelligent flexible
driver
Connectable wire
specifications (mm
2
)
Recommended wire
specifications (mm
2
)
Important
Wire specifications are determined per an ambient temperature of 50°C and an allowable wire
temperature of 75°C.
The main circuit of the inverter uses open type wiring terminals. For open type wiring terminals,
round crimp terminals are recommended. Refer to table 4-12 for round crimp terminals:
Table 4-12 Specifications of round crimp terminals
Wire cross-sectional area (mm
2
)
Terminal screw specifications
Specifications for round crimp
terminals