EasyManua.ls Logo

STEP ET Series - Page 43

Default Icon
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Wiring of Inverter
ET/EP/EH Series Intelligent Flexible Driver Manual
- 33 -
Inverter
model
EP6/ET6
inverter
capacity
(kW)
EH6
inverter
capacity
(kW)
Main fuse
Model
4T023
7.5
11
60
FWP-60B
4T031
11
15
60
FWP-60B
4T039
15
18.5
70
FWH-70B
4T045
18.5
22
100
FWH-100B
4T060
22
30
100
FWH-100B
4T075
30
37
100
FWH-100B
4T089
37
45
125
FWH-125B
4T103
45
55
150
FWH-150B
4T140
55
75
200
FWH-200B
4T168
75
90
250
FWH-250A
4T208
90
110
275
FWH-275A
4T250
110
132
325
FWH-325A
4T304
132
160
400
FWH-400A
4T377
160
200
500
FWH-500A
4T414
200
220
600
FWH-600A
4T477
220
250
600
FWH-600A
4T520
250
280
700
FWH-700A
4T605
280
315
800
FWH-800A
4T675
315
355
1000
170M5016
Emergency stop device
The overall design and installation must include an emergency stop device and other required safety
device. Controlling the motor by means of a key from the inverter operator, or by commands from
the I/O terminals or communications does not guarantee:
Achieving emergency stop of the motor.
Separating the inverter from dangerous voltages.
4.1.2.3 Input power cables/connections
The input cable connection can be any of the following:
The four-core cable (three-phase and grounding protection wire) does not require shielding
layer (if there are requirements for conducted and radiated disturbances, the shielding wire
needs to be configured).
Four-core insulated conductors installed in the conduit.
In any case, the conductor must be smaller than the maximum limit defined by the terminal size.
Motor cables should be used in derating when they are too long or when the cross-sectional area of
the motor cable is too large. Only cables with a specified cross-sectional area should be used for
inverters (see Table 4-11). Since the larger the cross-sectional area of the cable, the greater the
capacitance to ground and the greater the leakage current to ground, the use of cables with a larger
cross-sectional area should result in a lower output current, with a current reduction of about 5% for
each additional step in area. Table 4-11 lists the cable types for copper-core cables at different load
currents. The recommended models are only available for the cases listed in the upper part of the
table. It is not recommended to use aluminum-core cables.
Table 4-3 Corresponding load currents for cables
IEC
NEC
Based on:
Based on:

Table of Contents