Chapter 7 Parameter Explanation
ET/EP/EH Series Intelligent Flexible Driver Manual
- 83 -
3: PG vector control, supporting ABZ encoder, SINCOS encoder, and Rezav encoder.
5: No PG torque control, supporting synchronous motors and asynchronous motors.
6: Voltage and current sources, adapting to special applications, such as fire pump, current source,
voltage source, etc.
Function code
Name
Setting range
Factory setting
P10.01
Operation modes
0~4
0
P10.01 is used to set the mode of X0 (FWD) and X1 (REV) terminals to control the start and stop of
inverter when the terminal running command is given.
0: 2-wire type 1
XC
24V
XV
X0(P30.00=7)
X1(P30.01=8)
K1
K2
K2 K1
1 0
0 1
1 1
0 0
Inverter
Running
command
Stop
Reverse rotation
Forward rotation
Stop
Figure 7-1 Two-wire Running Mode 1
1: 2-wire type 2
XC
24V
XV
X0(P30.00=7)
X1(P30.01=8)
K1
K2
K2 K1
1 0
0 1
1 1
0 0
Inverter
Running
command
Stop
Stop
Forward rotation
Reverse rotation
Figure 7-2 Two-wire Running Mode 2
2: 3-wire type 1
The Xi (i=2 - 7) terminal is set to "9: three-wire run control".
When K3 is closed, K0 (FWD) and K1 (REV) control is effective; when K3 is disconnected, K0 and
K1 control is invalid and the inverter stops running;
The rising edge of X0 terminal indicates the forward run command; the rising edge of X1 terminal
indicates the reverse run command.
XC
24V
XV
X0(P30.00=7)
Xi
K3
K2
X1(P30.01=8)
K1
Inverter