Chapter 7 Parameter Explanation
ET/EP/EH Series Intelligent Flexible Driver Manual
- 83 -
3: PG vector control, supporting ABZ encoder, SINCOS encoder, and Rezav encoder.
5: No PG torque control, supporting synchronous motors and asynchronous motors.
6: Voltage and current sources, adapting to special applications, such as fire pump, current source,
voltage source, etc.
P10.01 is used to set the mode of X0 (FWD) and X1 (REV) terminals to control the start and stop of
inverter when the terminal running command is given.
0: 2-wire type 1
变频器
XC
24V
XV
X0(P30.00=7)
X1(P30.01=8)
K1
K2
运行命令
停止
反转
正转
停止
K2 K1
1 0
0 1
1 1
0 0
Figure 7-1 Two-wire Running Mode 1
1: 2-wire type 2
变频器
XC
24V
XV
X0(P30.00=7)
X1(P30.01=8)
K1
K2
运行命令
停止
停止
正转
反转
K2 K1
1 0
0 1
1 1
0 0
Figure 7-2 Two-wire Running Mode 2
2: 3-wire type 1
The Xi (i=2 - 7) terminal is set to "9: three-wire run control".
When K3 is closed, K0 (FWD) and K1 (REV) control is effective; when K3 is disconnected, K0 and
K1 control is invalid and the inverter stops running;
The rising edge of X0 terminal indicates the forward run command; the rising edge of X1 terminal
indicates the reverse run command.
变频器
XC
24V
XV
X0(P30.00=7)
Xi
K3
K2
X1(P30.01=8)
K1