Chapter 7 Parameter Explanation
Shanghai Sigriner STEP Electric Co., Ltd.
- 128 -
Bus undervoltage threshold (V)
The default bus undervoltage threshold for 400V class inverter is 380V.
Power grid imbalance threshold
(%)
Determine the power grid imbalance fault according to the power grid voltage sampling, the
threshold can be set according to the on-site power grid conditions.
After the inverter runs, if the output current is 0, the inverter will report 51# fault after the delay of
parameter PWM detection.
Current-limiting frequency
reduction threshold (%)
Current limiting recovery
threshold
P70.23 - P70.27 are overcurrent frequency reduction related parameters, Bit0 setting of P70.08 is
required to enable this function. If current exceeds P70.23, the frequency reduction function is enabled.
Power grid overvoltage threshold
Overtemperature frequency
reduction starting temperature
Over-temperature frequency
reduction recovery temperature
Over-temperature frequency
reduction slope
Up-frequency overtemperature
threshold
Overtemperature detection
interval
When Bit1 of P70.08 is 1, the overtemperature frequency reduction function is enabled;
When the module temperature exceeds P70.32 (up-frequency overtemperature threshold), the speed
curve pauses and up-frequency stops;
When the module temperature is higher than P70.29 (overtemperature frequency reduction starting
temperature), frequency reduction starts, up to the lower limit frequency, with frequency reduction
cycle being P70.33 and each frequency reduction quantity being P70.31;
When the module temperature is lower than P70.30, frequency reduction ends, and according to the