48
table 6-1 Cable Specification of Single-branch Version
Cable
Specifications
Connec-
tion
holes
Requ.
Note
DC input
The cross-sectional area of
the positive and negative in-
put cables is 240 mm
2
(or 600
kcmil)at most
Eight wir-
ing inputs,
each with
two holes
arranged
up and
down for
positive
and nega-
tive
polarity
Φ13
Alumi-
num/
Copper
cables
can be
flexibly
selected
to bear
the max
current.
AC output
The cross-sectional area of
each phase inputs is 240 mm
2
(or 600 kcmil)at most (PCS
stand-alone AC output side)
Six inputs,
each with
two holes
arranged
up and
down for
each
phase
wiring.
Φ13
Alumi-
num/
Copper
cables
can be
flexibly
selected
to bear
the max
current.
RS485 communica-
tion cable
2-core twisted shielded pair
cable
- - -
Can communication
cable
0.75 mm
2
- - -
Network cable Standard network cable
- - -
6 Electrical Connection User Manual