EasyManua.ls Logo

Sungrow SG5.0RT - Page 70

Sungrow SG5.0RT
105 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
60
Table 7-2 "Q(P)" Mode Parameters Explanation
PPaarraammeetteerr EExxppllaannaattiioonn RRaannggee
Q(P) Curve Select corresponding curve according to local
regulations
A, B, C
*
QP_P1 Output power at point P1 on the Q(P) mode curve
(in %)
20.0 %–100.0
%
QP_P2 Output power at point P2 on the Q(P) mode curve
(in %)
20.0 %–100.0
%
QP_P3 Output power at point P3 on the Q(P) mode curve
(in %)
20.0 %–100.0
%
QP_K1 Power factor at point P1 on the Q(P) mode curve Curve A/C:
0.800 to 1.000
Curve B: -0.600
to 0.600
QP_K2 Power factor at point P2 on the Q(P) mode curve
QP_K3 Power factor at point P3 on the Q(P) mode curve
QP_
EnterVoltage
Voltage for Q(P) function activation (in %)
100.0 %–110.0
%
QP_
ExitVoltage
Voltage for Q(P) function deactivation (in %)
90.0 %–100.0
%
QP_
ExitPower
Power for Q(P) function deactivation (in %)
1.0 %–20.0 %
QP_
EnableMode
Unconditional activation/deactivation of Q(P)
function
Yes, No
* Curve C is reserved and consistent with Curve A currently.
7 iSolarCloud App User Manual

Table of Contents

Related product manuals