3
TimeSource 3100 87
Installation
097-72020-01 Issue 9: November 2003
2
5
3
SSSSSSSSSSS SSSS S SSSSS SSSS SSS S SSS S SSSSS S
26 Ports 5001, 5002, 5003 and 5004 on the TimeSource 3100 are used as though they were
serial TL1 communication ports. The following values are set at the factory and appear at
reset:
COMPRI=ALW1 (normal communication, including autonomous messages)
MONMSG=INH (monitors only the current port for messages)
KEEPALIVE=0 (does not send a COMPLD message to keep connection open)
ENDOFTEXT=0 (does not include an end-of-text code with a TL1 message)
ECHO=ALW (echoes characters back to the sending terminal)
AUTOLOGOFF=20 (does not log off the user during inactivity)
SWCONTROL=INH (uses no flow control)
If these values require change, use the Edit Communication command to set
communications parameters for TL1 communications.
ED-COM::COM-a:<ctag>:::[MONMSG=b[,]][KEEPALIVE=c[,]]
[ENDOFTEXT=d[,]][ECHO=b[,]][COMPRI=e[,]][AUTOLOGOFF=c[,]] [SWCONTROL=b];
COM-a=User IP port (a = 5001, 5002, 5003 or 5004)
MONMSG=b= Monitors messages on all ports (b = ALW), or current port (b = INH)
KEEPALIVE=c=Inactive minutes until the unit sends a COMPLD message to keep the
connection from being closed (c = 0 to 255)
ENDOFTEXT=d=Hex code added to responses before semicolon (d = 0 (disabled) to 9F)
ECHO=b=Echoes characters received so they appear on the user's screen as typed (b =
ALW), or inhibits echo (b = INH)
COMPRI=e=Sets the communication port capabilities as follows:
ALW0= normal communication, no autonomous messages
ALW1= normal communication, autonomous messages
ALW2= autonomous messages received, logged on or not
INH = closes connection and keeps port from use (command must go to another port) (if
the port is in use, this command also logs off the user)
AUTOLOGOFF=c=Inactive minutes until the unit logs off the user, keeping the connection
open (c = 0 to 255)
SWCONTROL=b=uses software (XON/XOFF) flow control (b = ALW), or no flow control (b
= INH)
Procedure E. Power-Up (cont’d)
Step Procedure

Table of Contents

Other manuals for Symmetricom TimeSource 3100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeSource 3100 and is the answer not in the manual?

Symmetricom TimeSource 3100 Specifications

General IconGeneral
BrandSymmetricom
ModelTimeSource 3100
CategoryGPS
LanguageEnglish

Related product manuals