User’s manual 82 UPS EVO DSP PLUS Modular
11.5 Low Battery and Automatic Restart
EVO DSP PLUS Modular reaches the Low Battery condition whenever, during working in Battery Mode, the Batteries
reach a charge level allowing the connected devices to operate for few minutes more. See chapter 5.2.5.3
“SETUP-BATTERY Submenu” for setting the parameters to manage the Low Battery condition.
The UPS warns operators of the Low Battery condition by:
• acoustic signal every 0.5 seconds
• flashing of the red Led BATTERY on the Control Panel
If AC Input does not come back on within few minutes, the UPS shuts-down automatically thus preventing the
batteries from discharging excessively; the UPS stops supplying Output power, deactivates Control Panel indication
and goes to a waiting state. Once AC Input comes back on, the UPS restarts automatically and after some seconds
it goes back to work in Line Mode.
After a complete discharge, the UPS needs 10 hours to recharge completely the batteries. The UPS recharges
batteries automatically if it works in Line Mode or in Bypass Mode.
11.6 Load Control
The UPS accepts Overload according to the operating Mode and to the duration of the Overload condition as
reported in chapter 12 “Technical Characteristics”.
if the Overload continues beyond the specified time the UPS switches automatically to the Bypass Mode.
Once the requested power is back within range, the UPS switches automatically to the Line Mode.
Make sure that the UPS never indicates Overload condition.
Do not connect a load greater than rated value to the UPS (see POWER specifications in
the chapter 12 “Technical Characteristics”), as this may damage the unit. In this case
the warranty is void.