User’s manual 88 UPS EVO DSP PLUS Modular
3 Phases four-wire, sharing Neutral with the Rectifier input and providing Neutral
reference to the Output
Nominal Voltage (Phase-Phase)
380 / 400 / 415 Vac (selectable)
Nominal Voltage (Phase-Neutral)
220 / 230 / 240 Vac (selectable)
+10% / +15% / +20%; default: +15% (selectable)
-10% / -20% / -30%; default: -20% (selectable)
50Hz/60Hz (Auto-selectable)
+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz) (selectable)
1 hour for 105 ~110%, 10 mins for 111~125%, 1 min for 126~150%, 200ms for >150%
Transfer Time (between Bypass and
Inverter)
Synchronous transfer: ≤ 20ms
Lead acid, sealed, free maintenance – 12 Vdc
40 batteries (4 Battery Modules)
Battery Charge Time (typical)
8A for each 30KVA Power Module; 6A for each 20KVA Power Module
Storage Temperature Range
-25°C to +55°C (-15°C to 40°C recommended for longer Battery life)
Operating Temperature Range
0°C to +40°C (20°C to 25°C recommended for longer Battery life)
0% - 95% (not condensing)
Audible Noise (at 1 meter)
Low Voltage (Safety) Directive 2014/35/EU
EMC (Electro-Magnetic Compatibility) Directive 2014/30/EU - category C3
1 RS232 port and 1 USB port
Included UPS Management Software,
compatible with: Windows, Linux, Unix, etc.
EPO (Emergency Power OFF)
Manual Bypass for Maintenance