16-18 Motor Thermal
Range: Function:
0 %* [0 - 100 %] View the calculated thermal load on the motor. The cut-out limit is 100%.
The basis for calculation is the ETR function selected in par.1-90
Motor
Thermal Protection.
16-22 Torque [%]
Range: Function:
0 %* [-200 - 200 %] This is a read out parameter only.
Shows the actual torque yielded in percentage of the rated torque, based
on the setting of the motor size and rated speed in par.1-20
Motor Power
[kW] or par.1-21 Motor Power [HP] and par.1-25 Motor Nominal Speed.
This is the value monitored by the
Broken Belt Function
set in par. 22-6*.
16-3* Drive Status
Parameters for reporting the status of the frequency converter.
16-30 DC Link Voltage
Range: Function:
0 V* [0 - 10000 V] View a measured value. The value is filtered with an 30 ms time constant.
16-32 Brake Energy /s
Range: Function:
0.000
kW*
[0.000 - 10000.000 kW] View the brake power transmitted to an external brake resistor, stated as
an instantaneous value.
16-33 Brake Energy /2 min
Range: Function:
0.000
kW*
[0.000 - 10000.000 kW] View the brake power transmitted to an external brake resistor. The mean
power is calculated on an average basis for the most recent 120 seconds.
16-34 Heatsink Temp.
Range: Function:
0 C* [0 - 255 C] View the frequency converter heatsink temperature. The cut-out limit is
90 ± 5 °C, and the motor cuts back in at 60 ± 5 °C.
16-35 Inverter Thermal
Range: Function:
0 %* [0 - 100 %] View the percentage load on the inverter.
16-36 Inv. Nom. Current
Range: Function:
10.00 A* [0.01 - 10000.00 A] View the inverter nominal current, which should match the nameplate
data on the connected motor. The data are used for calculation of torque,
motor protection, etc.
16-37 Inv. Max. Current
Range: Function:
16.00 A* [0.01 - 10000.00 A] View the inverter maximum current, which should match the nameplate
data on the connected motor. The data are used for calculation of torque,
motor protection, etc.
Parameter Description
172 TR200 Programming Guide