16-38 SL Controller State
Range: Function:
0 N/A* [0 - 100 N/A] View the state of the event under execution by the SL controller.
16-39 Control Card Temp.
Range: Function:
0 C* [0 - 100 C]
View the temperature on the control card, stated in °C.
16-40 Logging Buffer Full
Option: Function:
View whether the logging buffer is full (see parameter group 15-1*). The
logging buffer will never be full when par.15-13
Logging Mode is set to
Log always
[0].
[0] * No
[1] Yes
16-49 Current Fault Source
Range: Function:
0 N/A* [0 - 8 N/A] Value indicates source of current fault, including: short circuit, over cur-
rent and phase imbalance (from left): [1-4] Inverter, [5-8] Rectifier, [0] No
fault recorded
After a short circuit alarm (imax2) or over current alarm (imax1 or phase imbalance) this will contain the power
card number associated with the alarm. It only holds one number so it will indicate the highest priority power
card number (master first). The value will persist on power cycle but if a new alarm occurs it will be overwritten
with the new power card number (even if it a lower priority number). The value will only be cleared when the
alarm log is cleared (i.e. a 3-finger reset would reset the readout to 0).
16-5* Ref. & Feedb.
Parameters for reporting the reference and feedback input.
16-50 External Reference
Range: Function:
0.0 N/A* [-200.0 - 200.0 N/A] View the total reference, the sum of digital, analog, preset, bus and freeze
references, plus catch-up and slow-down.
16-52 Feedback [Unit]
Range: Function:
0.000
Proc-
essCtrlU-
nit*
[-999999.999 - 999999.999
ProcessCtrlUnit]
View value of resulting feedback value after processing of Feedback 1-3
(see par.16-54
Feedback 1 [Unit], par.16-55 Feedback 2 [Unit] and par.
16-56) in the feedback manager.
See par. 20-0*
Feedback
.
The value is limited by settings in par. 20-13 and par. 20-14. Units as set
in par.20-12
Reference/Feedback Unit.
16-53 Digi Pot Reference
Range: Function:
0.00 N/
A*
[-200.00 - 200.00 N/A] View the contribution of the Digital Potentiometer to the actual reference.
Parameter Description