The contents of counters can be displayed as bars on keypad. Select
Quick Menu
>
Loggings
:
Trending Continued
Bin / Trending Timed Bin / Trending Comparison
.
Note
The counters starts counting whenever the frequency converter is powered-up. Power cycle shortly after a reset
will zero the counters. EEProm data are updated once per hour.
23-60 Trend Variable
Option: Function:
Select the desired operating variable to be monitored for Trending.
[0] * Power [kW] Power yielded to the motor. Reference for the relative value is the rated
motor power programmed in par.1-20
Motor Power [kW] or par.
1-21
Motor Power [HP]. Actual value can be read in par.16-10 Power
[kW] or par.16-11 Power [hp].
[1] Current [A] Output current to the motor. Reference for the relative value is the rated
motor current programmed in par.1-24
Motor Current. Actual value can
be read in par.16-14
Motor Current.
[2] Frequency [Hz] Output frequency to the motor. Reference for the relative value is the
maximum output frequency programmed in par.4-14
Motor Speed High
Limit [Hz]. Actual value can be read in par.16-13 Frequency.
[3] Motor Speed [RPM] Speed of the motor. Reference for relative value is the maximum motor
speed programmed in par.4-13
Motor Speed High Limit [RPM].
23-61 Continuous Bin Data
Range: Function:
0 N/A* [0 - 4294967295 N/A] Array with 10 elements ([0]-[9] below parameter number in display).
Press OK and step between elements by means of
▲
and
▼
buttons on
the keypad.
10 counters with the frequency of occurrence for the operating variable
monitored, sorted according to the following intervals:
Counter [0]: 0% - <10%
Counter [1]: 10% - <20%
Counter [2]. 20% - <30%
Counter [3]: 30% - <40%
Counter [4]: 40% - <50%
Counter [5]: 50% - <60%
Counter [6]. 60% - <70%
Counter [7]: 70% - <80%
Counter [8]. 80% - <90%
Counter [9]: 90% - <100% or Max
The above minimum limits for the intervals are the default limits. These
can be changed in par.23-65
Minimum Bin Value.
Starts to count when the frequency converter is powered up for the first
time. All counters can be reset to 0 in par.23-66
Reset Continuous Bin
Data.
Parameter Description
232 TR200 Programming Guide