The contents of counters can be displayed as bars on keypad. Select
Quick Menu
>
Loggings
:
Trending Continued
Bin / Trending Timed Bin / Trending Comparison
.
Note
The counters starts counting whenever the frequency converter is powered-up. Power cycle shortly after a reset
will zero the counters. EEProm data are updated once per hour.
23-60 Trend Variable
Option: Function:
Select the desired operating variable to be monitored for Trending.
[0] * Power [kW] Power yielded to the motor. Reference for the relative value is the rated
motor power programmed in par.1-20
Motor Power [kW] or par.
1-21
Motor Power [HP]. Actual value can be read in par.16-10 Power
[kW] or par.16-11 Power [hp].
[1] Current [A] Output current to the motor. Reference for the relative value is the rated
motor current programmed in par.1-24
Motor Current. Actual value can
be read in par.16-14
Motor Current.
[2] Frequency [Hz] Output frequency to the motor. Reference for the relative value is the
maximum output frequency programmed in par.4-14
Motor Speed High
Limit [Hz]. Actual value can be read in par.16-13 Frequency.
[3] Motor Speed [RPM] Speed of the motor. Reference for relative value is the maximum motor
speed programmed in par.4-13
Motor Speed High Limit [RPM].
23-61 Continuous Bin Data
Range: Function:
0 N/A* [0 - 4294967295 N/A] Array with 10 elements ([0]-[9] below parameter number in display).
Press OK and step between elements by means of
and
buttons on
the keypad.
10 counters with the frequency of occurrence for the operating variable
monitored, sorted according to the following intervals:
Counter [0]: 0% - <10%
Counter [1]: 10% - <20%
Counter [2]. 20% - <30%
Counter [3]: 30% - <40%
Counter [4]: 40% - <50%
Counter [5]: 50% - <60%
Counter [6]. 60% - <70%
Counter [7]: 70% - <80%
Counter [8]. 80% - <90%
Counter [9]: 90% - <100% or Max
The above minimum limits for the intervals are the default limits. These
can be changed in par.23-65
Minimum Bin Value.
Starts to count when the frequency converter is powered up for the first
time. All counters can be reset to 0 in par.23-66
Reset Continuous Bin
Data.
Parameter Description
232 TR200 Programming Guide